Current Differential and Overcurrent Relay
- Two-,
Three-, and Four-Winding Current Differential Protection
Sensitive current differential protection with programmable single- or dual-slope
percentage restraint, supervised by a choice of second- and fourth-harmonic
blocking or restraint elements, plus fifth-harmonic and dc blocking elements
for secure protection of up to four windings. Phase current harmonic blocking
is set for either common or independent winding basis. Unrestrained high-set
differential elements provide fast operation for high-magnitude internal
faults. "Around the clock" phase angle compensation settings and automatic
tap calculations simplify settings.
- Individual
Winding Overcurrent Protection
Torque-controllable overcurrent elements, including one instantaneous, one
definite-time, and one inverse-time element each for phase, negative-sequence,
and residual ground currents, provide comprehensive overcurrent protection
on each winding input. Combined current feature sums current from two CTs
for ring-bus and breaker-and-a-half overcurrent applications.
- Through-Fault
Recording and Monitoring
Through-fault duty is recorded and accumulated for use in SELOGIC® control
equations or manual monitoring.
- Protection
and Control Logic
Restricted Earth Fault (REF) logic for sensitive grounded-wye winding ground
fault protection. SELOGIC Control
Equations with SELOGIC variables,
timers, latch bits, and remote control elements for customizing advanced
protection and control schemes. Local programmable control elements and programmable
text display points for advanced local operator interface.
- Metering
and Reporting
Oscillographic event reports (up to seven 60-cycle reports), Sequential Events
Recorder (SER) reporting, and accurate metering eliminate or reduce external
recorder and metering requirements. Station battery voltage monitor and circuit
breaker contact wear monitor provide important data for Reliability Centered
Maintenance (RCM) programs.
- ACSELERATOR® QuickSet™ Software
Develop relay settings off-line, program SELOGIC control equations, and analyze post-fault event reports.
|
- Thermal
modeling element for
key information about transformer overload capability.
- Panel-mount
or rack-mount hardware package.
- Chassis
available for one additional I/O board.
- I/O
board with contact sensing inputs and standard outputs,
or high-current interrupting outputs.
- Connectorized® packaging
(includes additional I/O inputs and output contacts).
- Additional
local and remote control switches and binary SER messaging.
- Distributed
Network Protocol (DNP) 3 Level 2 Slave communications
protocol available in SEL-387-5, -6 models.
- Conformal Coating (available in SEL-387-0, -5, -6 models.)—Protect equipment from harsh environments and airborne contaminants such as hydrogen sulfide, chlorine, salt, and moisture.
Learn more about conformal coating.

- Use
the thermal element to activate a control or issue a
warning or alarm when the transformer overheats or is
in danger of excessive insulation aging or loss of life.
Capture current, hourly or daily, data about your transformer
using the thermal event report.
- Apply
one SEL-387 Relay to protect any two-, three-, or four-winding
power transformer.
- Perform
predictive maintenance based on accumulated through-fault
duty as compared to transformer capability as defined
in ANSI Standard C57.109. Use recorded fault values or
an alarm set point to initiate an evaluation of transformer
maintenance needs.
- Protect
reactors, generators, large motors, and other multiterminal
power apparatus.
- Apply
with any combination of delta- or wye-connected CT secondary
circuits.
- Use
built-in winding overcurrent elements for backup protection.
- Use SELOGIC Control
Equations to create breaker failure logic.
- Detect
ground faults through delta-wye transformer banks, or
provide sensitive phase-to-phase protection, independent
of load current, with negative-sequence overcurrent element.
- Use
low-side overcurrent elements for backup distribution
bus or feeder protection.
- Use
any one of up to six independent setting groups to quickly
adapt the relay to different application scenarios.
- Use SEL-5040
Power System Report Manager Software to automatically
gather relay event reports on your PC and manage them
with a database.
- Use SEL-5010
Relay Assistant Software to manage your relay settings.
- Use SEL-5601
Analytic Assistant Software to display oscillograms
and vector diagrams to analyze event reports.


Budgetary
Retail, Quantity 1: $5,000
Fully Optioned Price: $6,280
(Prices displayed are for planning purposes
and are subject to change. Contact your SEL
sales representative today for a quote on configurations
and quantities to meet your needs.)

|
Some of the following documents require the use of Adobe® Reader.®
Get the free reader here. |



|

Front View - Panel-Mount
Rear View - Conventional Terminal Blocks (2U)
Rear View - Conventional Terminal Blocks - Additional I/O (3U)
Rear View - Connectorized® - Additional I/O (3U)
Dimensions

|
|
|

2350 NE Hopkins Court - Pullman, WA 99163 – USA
Phone: +1.509.332.1890 - Fax: +1.509.332.7990
|
|